Violation Detail
Standard Cited: 19100305 G01 IV A Wiring methods, components, and equipment for general use.
Inspection Nr: 1554982.015
Citation: 01001
Citation Type: Serious
Abatement Date: 12/06/2021 2
Initial Penalty: $2,341.00
Current Penalty: $1,638.70
Issuance Date: 11/19/2021
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC):
Gravity: 5
Report ID: 0523900
Contest Date:
Final Order: 12/09/2021
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/09/2021 | $1,638.70 | 12/06/2021 | Serious | |
Penalty | Z: Issued | 11/19/2021 | $2,341.00 | 12/06/2021 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a) Fuel Tank Area; On or about September 7, 2021, a flexible extension cord and a GFCI 3-outlet adapter were connected in series to provide permanent power to a pump located on a 500 gallon diesel fuel tank.