Violation Detail
Standard Cited: 19100333 B02 II C Selection and use of work practices
Inspection Nr: 1361168.015
Citation: 01001B
Citation Type: Serious
Abatement Date: 03/27/2019 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 03/13/2019
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC): A
Gravity: 10
Report ID: 0627100
Contest Date:
Final Order: 04/08/2019
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 04/08/2019 | $0.00 | 03/27/2019 | Serious | |
Penalty | Z: Issued | 03/13/2019 | $0.00 | 03/27/2019 | Serious |
Text For Citation: 01 Item/Group: 001B Hazard:
29 CFR 1910.333(b)(2)(ii)(C): Stored electric energy which might endanger personnel was not released. Capacitors were not discharged and high capacitance elements were not short-circuited and grounded. For the employees working on the 13,800 Volt switch gear on or about November 19, 2018 and times prior there to; The employer did not require the high capacitance elements to be short circuited and grounded prior to working inside the switch gear to repair the switch.