Violation Detail
Standard Cited: 19100333 B02 IV B Selection and use of work practices
Inspection Nr: 1361168.015
Citation: 01001C
Citation Type: Serious
Abatement Date: 03/27/2019 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 03/13/2019
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC): A
Gravity: 10
Report ID: 0627100
Contest Date:
Final Order: 04/08/2019
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 04/08/2019 | $0.00 | 03/27/2019 | Serious | |
Penalty | Z: Issued | 03/13/2019 | $0.00 | 03/27/2019 | Serious |
Text For Citation: 01 Item/Group: 001C Hazard:
29 CFR 1910.333(b)(2)(iv)(B): Before circuits or equipment was worked as deenergized, a qualified person did not use test equipment to test the circuit elements and electrical parts of equipment to which employees would be exposed and did not verify that the circuit elements and equipment parts were deenergized. For the employees working on the 13,800 Volt switch gear on or about November 19, 2018, and times prior thereto: The employer did not provide test equipment to test the circuit elements to verify all circuits and capacitors were deenergized.