Standard Cited: 19100335 A01 I Safeguards for personnel protection.
Inspection Nr: 1361168.015
Citation: 01002B
Citation Type: Serious
Abatement Date: 03/27/2019 2
Initial Penalty: $10,210.00
Current Penalty: $0.00
Issuance Date: 03/13/2019
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC): A
Gravity: 10
Report ID: 0627100
Contest Date:
Final Order: 04/08/2019
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 04/08/2019 | $0.00 | 03/27/2019 | Serious | |
Penalty | Z: Issued | 03/13/2019 | $10,210.00 | 03/27/2019 | Serious |
Text For Citation: 01 Item/Group: 002B Hazard:
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed: For the employees repairing the 13,800 Volt switch gear on or about November 19, 2018 and times prior thereto; The employer did not require the use of a protective body suit for employees working on high voltage electrical equipment that had not been verified through testing as deenergized.