Violation Detail
Standard Cited: 19100106 E02 II B 2 Flammable liquids.
Inspection Nr: 1460656.015
Citation: 01003
Citation Type: Other
Abatement Date: 06/12/2020 2
Initial Penalty: $10,603.00
Current Penalty: $7,518.20
Issuance Date: 05/18/2020
Nr Instances: 1
Nr Exposed: 150
Related Event Code (REC):
Gravity:
Report ID: 0522000
Contest Date:
Final Order: 06/15/2020
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/15/2020 | $7,518.20 | 06/12/2020 | Other | |
Penalty | Z: Issued | 05/18/2020 | $10,603.00 | 06/12/2020 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.106(e)(2)(ii)(b)(2): "Incidental storage or use of flammable liquids" -: The quantity of liquid that may be located outside of an inside storage room or storage cabinet in a building or in any one fire area of a building shall not exceed: 120 gallons of Category 2, 3, or 4 flammable liquids in containers. a) On or about February 4, 2020 the employer did not ensure that quantities of a Category 3 flammable liquid did not exceed 120 gallons outside of an inside storage room or storage cabinet in that 1,250 gallons of liquid Styrene (Category 3) was stored outside of an inside storage room or storage cabinet.