Violation Detail
Standard Cited: 19100253 B02 II Oxygen-fuel gas welding and cutting.
Inspection Nr: 1392072.015
Citation: 01003A
Citation Type: Serious
Abatement Date: 10/18/2019 2
Initial Penalty: $3,978.00
Current Penalty: $1,989.00
Issuance Date: 10/07/2019
Nr Instances: 3
Nr Exposed: 4
Related Event Code (REC):
Gravity: 10
Report ID: 0420600
Contest Date:
Final Order: 10/30/2019
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/30/2019 | $1,989.00 | 10/18/2019 | Serious | |
Penalty | Z: Issued | 10/07/2019 | $3,978.00 | 10/18/2019 | Serious |
Text For Citation: 01 Item/Group: 003A Hazard:
29 CFR 1910.253(b)(2)(ii): Inside of buildings, cylinders shall be stored in a well-protected, well-ventilated, dry location, at least 20 (6.1 m) feet from highly combustible materials such as oil or excelsior. Cylinders should be stored in definitely assigned places away from elevators, stairs, or gangways. Assigned storage spaces shall be located where cylinders will not be knocked over or damaged by passing or falling objects, or subject to tampering by unauthorized persons. Cylinders shall not be kept in unventilated enclosures such as lockers and cupboards: 203 W. Taft Vineland Rd. - Employees wee exposed to struck-by hazards, in that, compressed gas cylinders were stored in an unventilated 40 foot shipping container and oxygen and acetylene compressed gas cylinders were not secured from falling, observed on or about April 10, 2019.