Violation Detail
Standard Cited: 19100165 B01 Employee alarm systems.
Inspection Nr: 1663647.015
Citation: 01003B
Citation Type: Serious
Abatement Date: 03/01/2024
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 09/29/2023
Nr Instances: 1
Nr Exposed: 40
Related Event Code (REC):
Gravity: 5
Report ID: 0215800
Contest Date:
Final Order: 11/01/2023
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | P: Petition to Mod Abatement | 12/15/2023 | $0.00 | 03/01/2024 | Serious | |
Penalty | I: Informal Settlement | 11/01/2023 | $0.00 | 11/17/2023 | Serious | |
Penalty | Z: Issued | 09/29/2023 | $0.00 | 11/17/2023 | Serious |
Text For Citation: 01 Item/Group: 003B Hazard:
29 CFR 1910.165(b)(1): The employee alarm system did not provide warning for necessary emergency action as called for in the emergency action plan, or for reaction time for safe escape of employees from the workplace or the immediate work area, or both: a) On or about 4/5/2023, Various Cellars and Cold Storage rooms containing components of an Anhydrous Ammonia refrigeration system were not provided with sensors to detect the release of Anhydrous Ammonia. Abatement certification is required for this item.