Violation Detail
Standard Cited: 19100303 B02 General.
This violation item has been deleted.
Inspection Nr: 1469312.015
Citation: 01004
Citation Type: Serious
Abatement Date: 08/07/2020 2
Initial Penalty: $6,361.00
Current Penalty: $0.00
Issuance Date: 06/22/2020
Nr Instances: 1
Nr Exposed: 7
Related Event Code (REC):
Gravity: 1
Report ID: 0522000
Contest Date:
Final Order: 07/15/2020
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 07/15/2020 | $0.00 | 08/07/2020 | Serious | |
Penalty | Z: Issued | 06/22/2020 | $6,361.00 | 08/07/2020 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling. a) On or about June 1, 2020, the employer was using the Leviton N1302 Single Phase Motor Starter without overload protection as an electrical disconnect for 480 volts 3 phase power going to the Kentwood Moulder M609HS. The starter was not designed to be used as the sole means for electrical disconnect during work where locking out of energy is required, and it is not designed for use with 3 phase power.