Violation Detail
Standard Cited: 19100303 G01 I A General.
Inspection Nr: 1139851.015
Citation: 01005
Citation Type: Serious
Abatement Date: 05/25/2016 2
Initial Penalty: $3,000.00
Current Penalty: $2,100.00
Issuance Date: 05/13/2016
Nr Instances: 2
Nr Exposed: 12
Related Event Code (REC):
Gravity: 1
Report ID: 0418100
Contest Date:
Final Order: 06/10/2016
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/10/2016 | $2,100.00 | 05/25/2016 | Serious | |
Penalty | Z: Issued | 05/13/2016 | $3,000.00 | 05/25/2016 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized; the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: a. On or about 4/14/2016 in the storage room; employees were exposed to electrical shock hazards where the depth of the working space to access the right 208V/120V electrical panel was reduced to less than 36 inches by storage of merchandise. b. On or about 4/14/2016 in the storage room; employees were exposed to electrical shock hazards where the depth of the working space to access to the left electrical panel was reduced to less than 36 inches by storage of merchandise.