Violation Detail
Standard Cited: 19100304 F02 II Wiring design and protection.
Inspection Nr: 1199482.015
Citation: 01005
Citation Type: Other
Abatement Date: 3
Initial Penalty: $8,873.00
Current Penalty: $0.00
Issuance Date: 02/06/2017
Nr Instances: 1
Nr Exposed: 4
Related Event Code (REC):
Gravity:
Report ID: 0214500
Contest Date:
Final Order: 02/28/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 02/28/2017 | $0.00 | Other | ||
Penalty | Z: Issued | 02/06/2017 | $8,873.00 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.304(f)(2)(ii): The employer did not ensure that each protective device shall be capable of detecting and interrupting all values of current that can occur at its location in excess of its trip setting or melting point; (a) Computer Main Panel : Breaker on electric panel was locked in closed position by a screw placed to hold it. Conditions prevent the breaker from tripping to open in case of overcurrent creating fire and other electrical hazards, on or about December 22, 2016.