Violation Detail
Standard Cited: 19100333 A01 Selection and use of work practices
Inspection Nr: 1216924.015
Citation: 01005
Citation Type: Serious
Abatement Date: 11/01/2017 2
Initial Penalty: $12,675.00
Current Penalty: $9,506.25
Issuance Date: 08/30/2017
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC):
Gravity: 10
Report ID: 0936100
Contest Date:
Final Order: 10/02/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/02/2017 | $9,506.25 | 11/01/2017 | Serious | |
Penalty | Z: Issued | 08/30/2017 | $12,675.00 | 09/26/2017 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.333(a)(1): Live parts to which an employee may be exposed were not de-energized before the employee works on or near them: Pier 3, Crane 2, Machine House: On March 10, 2017, a crane heavy equipment mechanic removed a rear metal panel cover of the Transformer Secondary Substation System (TSS) equipment near two energized 4160 volts metallic bus bars. The TSS was not de-energized prior to the work, the mechanic contacted the bus bars and was electrocuted.