Violation Detail
Standard Cited: 19100335 A02 I Safeguards for personnel protection.
Inspection Nr: 1216924.015
Citation: 01008
Citation Type: Other
Abatement Date: 11/01/2017 2
Initial Penalty: $12,675.00
Current Penalty: $0.00
Issuance Date: 08/30/2017
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC): A
Gravity:
Report ID: 0936100
Contest Date:
Final Order: 10/02/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/02/2017 | $0.00 | 11/01/2017 | Other | |
Penalty | Z: Issued | 08/30/2017 | $12,675.00 | 09/26/2017 | Serious |
Text For Citation: 01 Item/Group: 008 Hazard:
29 CFR 1910.335(a)(2)(i): When working near exposed energized conductors or circuit parts, each employee did not use insulated tools or handling equipment if the tools or handling equipment might make contact with such conductors or parts. If the insulating capability of insulated tools or handling equipment is subject to damage, the insulating material shall be protected: Pier 3, Crane 2, Machine House: Insulated tools were not provided to the crane heavy equipment mechanic who worked near energized parts while he serviced the Transformer Secondary Substation System (TSS) equipment. The mechanic contacted the 4160 volt bus bars inside the TSS and was electrocuted.