Violation Detail
Standard Cited: 19100307 C Hazardous (classified) locations.
Inspection Nr: 1250461.015
Citation: 01008B
Citation Type: Serious
Abatement Date: 02/16/2018
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 01/17/2018
Nr Instances: 1
Nr Exposed: 12
Related Event Code (REC):
Gravity: 5
Report ID: 0215800
Contest Date: 02/06/2018
Final Order:
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | C: Contested | 02/08/2018 | $0.00 | 02/16/2018 | Serious | |
Penalty | Z: Issued | 01/17/2018 | $0.00 | 02/16/2018 | Serious |
Text For Citation: 01 Item/Group: 008B Hazard:
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: a) Process Room, on or about 7/26/17: The process area is a Class II Division 2 hazardous environment. The electrical disconnects and receptacles used within 10 feet of equipment such as but not limited to: Rotary Dryers, Hammer Mills, Dust Collectors, and Bagger were not intrinsically safe or approved for Class II, Division 2 hazardous locations.