Violation Detail
Standard Cited: 19100303 G01 I C General.
Inspection Nr: 1018261.015
Citation: 01010B
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/10/2015
Nr Instances: 3
Nr Exposed: 3
Related Event Code (REC):
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 07/30/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 07/30/2015 | $0.00 | Serious | ||
Penalty | Z: Issued | 07/10/2015 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 010B Hazard:
29 CFR 1910.303(g)(1)(i)(C): The work space provided for electrical equipment was not clear and did not extend from the grade, floor, or platform to the height required by paragraph (g)(1)(vi) of this section. Other equipment associated with the electrical installation and located above or below the electric equipment extended more than 153 mm (6 in.) beyond the front of the electric equipment: A. Building 50, Maintenance Workbench Area: On, or about, January 15, 2015, Hevi-Duty transformers had been installed in the working space for the following panelboards: 1. Cutler-Hammer 120/208 volt circuit breaker panel. 2. Cutler-Hammer 480/277 volt circuit breaker panel. B. Building 4: On, or about, January 20, 2015, an ITE transformer had been installed in the working space for a General Electric 120/208 circuit breaker panel.