Violation Detail
Standard Cited: 19100111 B08 II Storage and handling of anhydrous ammonia.
Inspection Nr: 901718.015
Citation: 01012
Citation Type: Serious
Abatement Date: 11/07/2013 2
Initial Penalty: $4,900.00
Current Penalty: $6,700.00
Issuance Date: 10/09/2013
Nr Instances: 6
Nr Exposed: 3
Related Event Code (REC):
Gravity: 10
Report ID: 0636900
Contest Date: 11/05/2013
Final Order: 06/20/2014
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 06/20/2014 | $6,700.00 | 11/07/2013 | Serious | |
Penalty | C: Contested | 11/08/2013 | $4,900.00 | 11/07/2013 | Serious | |
Penalty | Z: Issued | 10/09/2013 | $4,900.00 | 11/07/2013 | Serious |
Text For Citation: 01 Item/Group: 012 Hazard:
29 CFR 1910.111(b)(8)(ii): Hose assemblies, when made up, were not capable of withstanding a test pressure of 500 p.s.i.g. On or about April 17, 2013 and at times prior thereto, the employer did not ensure that when new Parker 7261 anhydrous ammonia system hoses were installed or replaced that they were tested to withstand a test pressure of at least 500 p.s.i.g.