Violation Detail
Standard Cited: 19100304 B04 II B Wiring design and protection.
This violation item has been deleted.
Inspection Nr: 1020632.015
Citation: 01013
Citation Type: Serious
Abatement Date: 06/29/2015
Initial Penalty: $3,400.00
Current Penalty: $0.00
Issuance Date: 06/03/2015
Nr Instances: 1
Nr Exposed: 5
Related Event Code (REC):
Gravity: 5
Report ID: 0936200
Contest Date: 06/26/2015
Final Order: 03/08/2016
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 03/08/2016 | $0.00 | 06/29/2015 | Serious | |
Penalty | C: Contested | 07/02/2015 | $3,400.00 | 06/29/2015 | Serious | |
Penalty | Z: Issued | 06/03/2015 | $3,400.00 | 06/29/2015 | Serious |
Text For Citation: 01 Item/Group: 013 Hazard:
29 CFR 1910.304(b)(4)(ii)(B): Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle may not supply a total cord- and plug-connected load in excess of the maximum specified in Table S-4: CWC 226, Artillery Repair: Employees were exposed to electrical shock where a 20 amp branch circuit supplying two or more receptacle outlets was supplying a load of 23.1 amps where table S-4 indicates the maximum load is 16 amps.