Violation Detail
Standard Cited: 19100303 B06 General.
Inspection Nr: 1058109.015
Citation: 01022
Citation Type: Serious
Abatement Date: 10/23/2015 2
Initial Penalty: $5,500.00
Current Penalty: $3,300.00
Issuance Date: 10/08/2015
Nr Instances: 3
Nr Exposed: 10
Related Event Code (REC):
Gravity: 5
Report ID: 0111100
Contest Date:
Final Order: 11/02/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 11/02/2015 | $3,300.00 | 10/23/2015 | Serious | |
Penalty | Z: Issued | 10/08/2015 | $5,500.00 | 10/23/2015 | Serious |
Text For Citation: 01 Item/Group: 022 Hazard:
29 CFR 1910.303(b)(6): Unless identified for use in the operating environment, conductors or equipment were located in damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other agents that had a deteriorating effect on the conductors or equipment; or where exposed to excessive temperatures: Conductors and equipment were not identified for use in the operating environment in the following instances: a) Raw Stock - The lighting conduit, located above the #3 raw stock thickener, was deteriorating due to the rising steam from the hot stock and water mixture. b) Raw Stock - Corroded cable tray supports detached from the structural steel. c) #8 Recovered Stock Chest - Three metal stands, supporting electrical equipment located in a wet environment, were corroded and broken from their respective bases.