Violation Detail
Standard Cited: 19100303 B07 IV General.
Inspection Nr: 1058109.015
Citation: 01023A
Citation Type: Serious
Abatement Date: 10/19/2015 2
Initial Penalty: $7,000.00
Current Penalty: $4,200.00
Issuance Date: 10/08/2015
Nr Instances: 11
Nr Exposed: 25
Related Event Code (REC): C
Gravity: 10
Report ID: 0111100
Contest Date:
Final Order: 11/02/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 11/02/2015 | $4,200.00 | 10/19/2015 | Serious | |
Penalty | Z: Issued | 10/08/2015 | $7,000.00 | 10/19/2015 | Serious |
Text For Citation: 01 Item/Group: 023A Hazard:
29 CFR 1910.303(b)(7)(iv): There were damaged parts that could adversely affect safe operation or mechanical strength of the equipment, such as parts that were broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating: Electrical equipment contained damaged parts in the following instances: a) C2 Color Preparation Basement - The cord on the sewer sampler was cracked and deteriorated. b) Old Bleachery, PCC Agitator Motor #1 - The mc cable was pulled away from the jag connector. c) Beater Room Control Room - The Kold Wave air conditioner had a damaged plug that was warped by heat. d) #7 & 8 Stock Prep Area - The #10 circuit breaker toggle, in the #8 MC Wet End electrical panel, was broken off. e) Old Grinder Room - The control cable, to the CM electrical hoist, had damaged cable insulation and deformed internal electrical conductors from being folded and secured with nylon ties. f) Dock Area, Dock Leveler #68 - The electrical cord for the light was damaged and the internal conductors were exposed. g) Satellite Garage - The parts cleaner electrical cord had damaged section of electrical cord exposing undamaged internal conductors. h) Machine Shop - The electrical liquidtight metallic conduit, at the lower part of the Van Norman milling machine, was held together by electrical tape and was damaged and separated from its connector. i) Machine Shop - The electrical liquidtight metallic conduit, at the upper part of the Van Norman milling machine, was damaged and separated from the connector exposing the conductors. j) Raw Stock - The insulated portion of the armored cable, to the Conveyor C- motor, was pulled out of the connector exposing the armor before the connector. k) Raw Stock - The energized 120 volt flood light, not approved for the wet/damp location, had a blown lamp that fell off its corroded base.