Violation Detail
Standard Cited: 19100303 B08 I General.
Inspection Nr: 1058109.015
Citation: 01024
Citation Type: Serious
Abatement Date: 10/19/2015 2
Initial Penalty: $7,000.00
Current Penalty: $3,320.00
Issuance Date: 10/08/2015
Nr Instances: 9
Nr Exposed: 30
Related Event Code (REC):
Gravity: 10
Report ID: 0111100
Contest Date:
Final Order: 11/02/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 11/02/2015 | $3,320.00 | 10/19/2015 | Serious | |
Penalty | Z: Issued | 10/08/2015 | $7,000.00 | 10/19/2015 | Serious |
Text For Citation: 01 Item/Group: 024 Hazard:
29 CFR 1910.303(b)(8)(i): Electrical equipment was not firmly secured to the surface on which it was mounted: Electrical equipment was not firmly secured to the surface on which it was mounted in the following instances: a) Catalog Stock Preparation - The mc cable was not secured. b) #5 Paper Machine, Drive Side - The mc cable was not secured. c) Catalog #4 Furnace Air Supply Fan- The mc cable was not secured. d) C2 Color Preparation, Basement - The T-55 station timer and outlet boxes were not firmly secured. e) #5 Paper Machine, Basement - The #5 and #6 outlet boxes were not secured. f) Pump House, Top Level - The mc cable for the electric heater was not secured. g) Pump House, First Sublevel - The mc cable for the light was not secured. h) Raw Stock - The energized 120 volt flood light, hanging by its conductors was not secured. i) C-2 Coater, 600 Volt Panel - The opening between the trim and can was not effectively closed.