Violation Detail
Standard Cited: 19100304 G05 Wiring design and protection.
Inspection Nr: 1058109.015
Citation: 01026A
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $7,000.00
Current Penalty: $4,200.00
Issuance Date: 10/08/2015
Nr Instances: 2
Nr Exposed: 2
Related Event Code (REC):
Gravity: 10
Report ID: 0111100
Contest Date:
Final Order: 11/02/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 11/02/2015 | $4,200.00 | Serious | ||
Penalty | Z: Issued | 10/08/2015 | $7,000.00 | Serious |
Text For Citation: 01 Item/Group: 026A Hazard:
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: The path to ground was not effective in the following instances: a) Hydropulper Area - The path to ground for the 110/575 volt wire cutter machine was not effective and the grounding pin was loose. b) Bond Kitchen Area - The path to ground from the 220 volt fan was not effective.