Violation Detail
Standard Cited: 19100304 F01 IV Wiring design and protection.
Inspection Nr: 1291102.015
Citation: 01031
Citation Type: Serious
Abatement Date: 09/17/2018 3
Initial Penalty: $3,880.00
Current Penalty: $3,880.00
Issuance Date: 07/24/2018
Nr Instances: 3
Nr Exposed: 15
Related Event Code (REC):
Gravity: 1
Report ID: 0625400
Contest Date:
Final Order: 08/24/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/24/2018 | $3,880.00 | 09/17/2018 | Serious | |
Penalty | Z: Issued | 07/24/2018 | $3,880.00 | Serious |
Text For Citation: 01 Item/Group: 031 Hazard:
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel: On or about January 30, 2018, a disconnect and two breaker boxes between the fabrication and maintenance shops were blocked by steel tables that were placed in front of them. The boxes did not have sufficient space for prompt access in front of them, exposing employees to hazards such as, but not limited to, delay in turning power off to a circuit.