Violation Detail
Standard Cited: 19100303 B07 IV General.
Inspection Nr: 1207843.015
Citation: 01039B
Citation Type: Serious
Abatement Date: 02/02/2018 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 06/26/2017
Nr Instances: 3
Nr Exposed: 12
Related Event Code (REC):
Gravity: 5
Report ID: 0215800
Contest Date: 07/09/2017
Final Order: 02/02/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 02/02/2018 | $0.00 | 02/02/2018 | Serious | |
Penalty | C: Contested | 07/26/2017 | $0.00 | 07/07/2017 | Serious | |
Penalty | Z: Issued | 06/26/2017 | $0.00 | 07/07/2017 | Serious |
Text For Citation: 01 Item/Group: 039B Hazard:
29 CFR 1910.303(b)(7)(iv): There were damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action or overheating: a) On or about 2/7/2017, Basement: An electrical cable tray located below the wet end was damaged in that its suspension rods were corroded, allowing the cable tray and associated wiring to no longer be supported. b) On or about 2/7/2017, Basement: An electrical cable tray located in the pump room was damaged in that its suspension rods and frame were corroded, allowing the cable tray and associated wiring to no longer be supported. c) On or about 2/15/2017, Maintenance area: An electrical cable tray located in the mezzanine area was damaged in that its suspension rod were no longer connected, allowing the cable tray and associated wiring to no longer be supported. Abatement certification is required for this item.