Violation Detail
Standard Cited: 19100305 G01 IV A Wiring methods, components, and equipment for general use.
Inspection Nr: 1207843.015
Citation: 02001
Citation Type: Other
Abatement Date: 04/03/2018 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 06/26/2017
Nr Instances: 5
Nr Exposed: 20
Related Event Code (REC):
Gravity:
Report ID: 0215800
Contest Date: 07/09/2017
Final Order: 02/02/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 02/02/2018 | $0.00 | 04/03/2018 | Other | |
Penalty | C: Contested | 07/26/2017 | $0.00 | 07/07/2017 | Other | |
Penalty | Z: Issued | 06/26/2017 | $0.00 | 07/07/2017 | Other |
Text For Citation: 02 Item/Group: 001 Hazard:
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) On or about 1/31/2017, Machine room: Extension cords and relocatable power taps were used in place of permanent wiring inside of the machine tender station. b) On or about 1/31/2017, Machine room: Extension cords were being used to energize lights in the rafters of the machine room, in place of permanent wiring. c) On or about 2/15/2017, Basement: An extension cord was used to provide power to the ClO2 generator in place of permanent wiring. d) On or about 2/15/2017, Maintenance shop: An extension cord and relocatable power tap were in use in the break room in place of permanent wiring. e) On or about 2/16/2017, Boiler house: A yellow extension cord was in use in the electrical room in place of permanent wiring. Abatement certification is required for these items.