Violation Detail
Standard Cited: 19100303 G02 I A General.
Inspection Nr: 1119628.015
Citation: 03009
Citation Type: Serious
Abatement Date: 08/29/2016 2
Initial Penalty: $7,000.00
Current Penalty: $4,200.00
Issuance Date: 07/13/2016
Nr Instances: 1
Nr Exposed: 4
Related Event Code (REC): C
Gravity: 10
Report ID: 0112000
Contest Date:
Final Order: 08/03/2016
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/03/2016 | $4,200.00 | 08/29/2016 | Serious | |
Penalty | Z: Issued | 07/13/2016 | $7,000.00 | 08/29/2016 | Serious |
Text For Citation: 03 Item/Group: 009 Hazard:
29 CFR 1910.303(g)(2)(i)(A): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or by location in a room, vault, or similar enclosure that is accessible only to qualified persons: Mezzanine Electrical Room: On, or about, January 15, 2016, unqualified employees accessed the electrical room to trouble shoot, reset and repair electrical distribution equipment related to the Coating Equipment. The room contained electrical equipment such as, but not limited to, circuit breaker panels installed without enclosures, circuit breakers mounted directly on control boards, open fuse holders and exposed fuses, live terminal strips, open disconnect switches, open motor starters, open relays and timers and open snap switches.