Inspection Detail
Inspection: 1276794.015 - High Grade Beverage, Inc.
Inspection Information - Office: Parsippany Area Office
Site Address:
High Grade Beverage, Inc.
86 Canfield Avenue
Randolph, NJ 07869
Mailing Address:
891 Georges Rd., North Brunswick, NJ 08902
Union Status: Union
SIC:
NAICS: 424810/Beer and Ale Merchant Wholesalers
Inspection Type: Fat/Cat
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 05/07/2018
Emphasis:
Case Closed: 02/08/2019
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 1283855 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 1 | ||||
Current Violations | 1 | 1 | ||||
Initial Penalty | $12,805 | $0 | $0 | $0 | $0 | $12,805 |
Current Penalty | $12,805 | $0 | $0 | $0 | $0 | $12,805 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19100332 B01 | 05/09/2018 | 06/06/2018 | $12,805 | $12,805 | $0 | Z - Issued |
Investigation Summary
At 1:00 p.m. on November 13, 2017, Employee #1 was replacing an emergency lighting fixture with a new fixture and accessed the wall-mounted unit via a scissors lift. Employee #1 was found lying on his back in the scissors lift, not breathing and pulseless, at approximately 10 feet in the air with the metallic BX cable carrying the 12 gauge single strand copper wire lying over the guardrail of the lift adjacent to the emergency lights. The black wire coming from BX conduit was live as shown by electricians summoned to the scene following the incident and the wire was carrying 277 Volts as defined by the markings on the Square D panel board. The panel board was located across the warehouse on the West wall and this work was being done not far from the East wall of the facility. When electricians got to the scene, the circuit breaker #36 which powers the emergency lighting circuit was not off and therefore found the black wire live. There was no evidence of gloves used as PPE or other PPE in the area and there were certainly no insulated gloves or even insulated tools seen in the area. Employee #1 was electrocuted and his body showed an entrance wound on this right hand and an exit wound on this left hand. The employee was found in cardiac arrest and was transported to the hospital where he was pronounced dead.
Keywords: Aerial Lift, Electrocuted, Lighting Fixture
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 1276794.015 | 55 | M | Fatality | Occupation Not Listed |