OSHA Requirements » Am I required to have an emergency action plan (EAP)? (Text Version)

Please review the following sections to determine if you are required to have an emergency action plan (EAP).

Ask the OSHA expert! A helpful alternative to answer the question: Am I required to have an EAP?

Section I

If there are NO fire extinguishers provided in the workplace, please answer the following questions.

Section II

If there ARE fire extinguishers provided in the workplace, BUT not intended for employee use, please answer the following questions.

Section III

If there ARE fire extinguishers provided in the workplace, AND intended for employee use, AND employees are required to evacuate the workplace, please answer the following questions.

Section IV

If there ARE fire extinguishers provided in the workplace, AND intended for employee use, BUT employees are NOT required to evacuate the workplace.

You are NOT REQUIRED to develop an emergency action plan (EAP). However, you must comply with all provisions in [29 CFR 1910.157]. Please click on the link for more information.

Questions

If you answer yes to ANY of the following questions, your company IS REQUIRED to have an Emergency Action Plan. Please click here to begin your Emergency Action Plan.

  • Does your facility use a total flooding extinguishing system that provides any one of the following design concentrations:
    • 4% or greater of Halon 1211?
    • 4% or greater of carbon dioxide?
    • 10% or greater of Halon 1301?
    • Concentrations exceeding 7% when egress from an area cannot be accomplished in one minute?
  • Does your facility use a fire detection system with alarms or devices that are delayed by more than 30 seconds for reasons other than a total flooding extinguishing system listed above?
  • Are you required to comply with [29 CFR 1910.119] Process Safety Management?
  • Are you required to comply with [29 CFR 1910.272] Grain Handling Facilities?
  • Are you required to comply with [29 CFR 1910.1047] Ethylene Oxide?
  • Are you required to comply with [29 CFR 1910.1050] Methylenedianiline?
  • Are you required to comply with [29 CFR 1910.1051] 1,3-Butadiene?
  • Do you plan to evacuate all of your employees and to rely on an outside party to provide emergency response to a hazardous substance release?

    NOTE: If a hazardous substance emergency could occur at your facility and you plan to have any of your employees participate in the emergency response, you are required to have an emergency response plan consistent with [29 CFR 1910.120(q)] (Hazardous Waste Operations and Emergency Response).

If you answered yes to ANY of the previous questions, your company IS REQUIRED to have an Emergency Action Plan. Please click here to begin your Emergency Action Plan.